Having looked at the PFD and P & ID Diagrams in our
previous posts, we can now discuss the loop diagrams also called the loop
sheets. Let's consider the diagram of a compressor surge system shown below:
From the loop diagram above we can see more
additional instruments that weren’t shown in the PFD and P & ID: We
have 2 transmitters, a controller, and a valve. We also have 2 signal
transducers. The first transducer 42a modifies the flow transmitter signal before it goes into the controller. and the second
transducer 42b converts the electronic 4-20mA signal into a pneumatic 3-15 PSI
air pressure signal. Each instrument ''bubble'' in a loop diagram represents an
individual device, with its own terminals for connecting wires.
The dashed lines represent individual copper wires
instead of whole cables. Terminal blocks where these wires connect to are
represented by squares with numbers in them. Cable numbers, wire colors,
junction block numbers, panel identification and even grounding points are all
shown in the loop diagrams. You can also notice from this loop diagram,
the action on each instrument. You will see a box and arrow (pointing either up
or down) next to each instrument bubble. An ” up” arrow (↑) represents a direct-acting instrument: one whose
output signal increases as the input stimulus increases. A down arrow (↓) represents a reverse-acting instrument, one whose
output signal decreases as the input stimulus increases.
All the instruments in this loop are direct-acting
with the exception of the pressure differential transmitter PDT-42. Here
the down arrow tell us that the transmitter will output a full-range signal (20
mA) when it senses zero differential pressure, and a 0% signal (4 mA) when it
sensing a full 200 PSI differential. Excessive pressure drop across the
compressor is considered dangerous because it may lead to the compressor
surging. For this reason, the controller will naturally take action to prevent
surge by commanding the anti-surge control valve to open, because it, “thinks”
the compressor is about to surge i.e. the transmitter is intentionally
calibrated to be reverse-acting such that any break in the signal wiring will
naturally bring the system to its safest condition.
The only diagram that can be more detailed than a
loop diagram is the electronic schematic diagram for an individual instrument
but then it shows details for that particular instrument alone, thus the loop
diagram is the most detailed form of diagram for any control system as a whole
and it must contain details omitted by PFDs and P & IDs.
No comments:
Post a Comment